Skip to main content
v5.32
operator
manufacturer
Last updated on

Dynamic Load Management

Managing power for multiple Charging Stations is challenging when current is limited. Bender’s Dynamic Load Management (DLM) system solves this by automatically adjusting charging currents to match available power.

Unlike traditional systems that need extra hardware or struggle with compatibility, the DLM is part of the Charge Controller's core functionality.

A designated Charging Station acts as the DLM Master, managing the others and communicating with an External Meter through standard interfaces like Modbus or Ethernet. The DLM Master collects real-time data every 30 seconds, including Charging Station occupancy, vehicle charging status, phases in use, and available power. It calculates and distributes power based on this data, ensuring efficient and balanced charging.

Example Scenarios:

  • Scenario 1: If one Charging Station is in use, the DLM Master provides the full 32A required for charging.
  • Scenario 2: If two or more Charging Stations are in use, the DLM Master divides the available 50A supply among the active stations.

1. Basic Setup

1.1. DLM Master/Slave Setup

Location in Config UIParameterValueInfo
LOAD MANAGEMENT > Dynamic Load ManagementDynamic Load Mangement - DLM Master/SlaveDLM Master (with internal DLM-Slave)The Charge Controller is part of the DLM and also regulates itself. This option is most commonly used.
DLM Master (Standalone)The Charge Controller is not part of the DLM. It only regulates other Charge Controller.
DLM Slave (Master-Auto-Discovery)The Slave Controller connects to the Master Controller with the same DLM Network Id. For this to work, the DLM Master needs to be fitted with a DLM Network Id. You can set a DLM Network Id under LOAD MANAGEMENT > Dynamic Load Management
DLM Slave (Master-Fixed-IP)he Slave Controller connects to the Master Controller that matches the DLM Master IP set under DLM Master IP and port . To set a fixed IP for the Master Controller, under NETWORK set Mode for ethernet configuration to Static. Under Static network configuration IP set your desired network IP.
caution

We advise you to leave Disable Discovery Broadcasting turned Off. Otherwise the installation of a connection can not be assured.

1.2. Phase rotation

Charging Stations are designed to work with either one phase or three phases. A car can charge using one phase (L1) or three phases (L1, L2, L3), with the phases always positioned 120° apart.

To manage the load effectively and prevent unbalanced power distribution, the system needs to know how each Charging Station’s phases are set or aligned. Without this information, it becomes harder to optimize the charging current and ensure stable operation.

The load management system uses the phase position or rotation data for each Charging Station to evenly distribute the charging current. To further balance loads, the phases are rotated in the sub-distribution system, improving efficiency and stability.

Example:

Charging Station 1

L 1L 2L 3
L1L2L3

Charging Station 2

L 1L 2L 3
L2L3L1

Charging Station 3

L 1L 2L 3
L3L1L2

This rotation is done in order to distribute the load generated by single-phase charging cars as evenly as possible to all phases.

The parameter Phase rotation of the Charging Station is set in the Charging Station itself as the installer has intended for this Charging Station.

caution

Double Charging Stations may already be connected through phase rotation.

2. Configuration

The Setup and configuration can be done either locally via the web Interface or remotely using OCPP Change Configuration.

The following table offers an overview of the different available settings found under LOAD MANAGEMENT > Dynamic Load Management:

SettingInfo
Dynamic Load Management - DLM Master/Slave Specifies the ChargePoint's role in a DLM network. There MUST be exactly one DLM Master in a DLM network managing multiple DLM-Slaves.
DLM Network Id Several DLM groupings might coexist in one physical LAN. In case of DLM Master-Auto-Discovery, they are distinguished by Master-Auto-Discovery Network.
Disable Discovery Broadcasting Disables DLM Discovery beacons in the DLM master, preventing DLM slaves from automatically finding their DLM master using the DLM Master-Auto-Discovery feature.
Configure Solar Mode for DLM Specifies if the DLM master allows special handling of DLM slaves for solar energy. 'Only Solar Charging' enables these slaves to charge only when sufficient solar energy is available.
DLM Algorithm Sample Rate The DLM algorithm recalculates and reassigns current to its DLM slaves at this set rate, except for EVs preparing to charge, which are assigned current immediately.
EVSE Sub-Distribution Limit (L1/L2/L3) [A]Overall current limit for DLM available for distribution to EVs.
Operator EVSE Sub-Distribution Limit (L1/L2/L3) [A]Operator current limit for DLM available for distribution to EVs. The 'Operator EVSE Sub-Distribution Limit' is equal or smaller than the 'EVSE Sub-Distribution Limit'.
External Input 1 Config Adds a configurable offset to 'EVSE Sub-Distribution Limit' based on GPI External Input 1.
External Input 1 Polarity Changes the polarity of the input signal 1. "Active high" does not change the polarity, "Active low" inverts the signal.
Ext. Input 1 Current Offset (L1/L2/L3) [A]Offset added to 'EVSE Sub-Distribution Limit' case external input 1 is high.
Solar Mode on this charger Enables additional limiting for this DLM slave to use renewable production.
External Meter Support If enabled, a secondary meter considers additional load power consumption, adjusting EV charging power. Ensure 'Meter configuration (Second)' is set, preferably to a 3-phase, phase-aware meter.
Meter configuration (Second)Energy Management: the type of second meter used only for input to manage the current on the grid. For Modbus/RTU meters the address must be 2.
Main Distribution Limit (L1/L2/L3) [A]Current limit for DLM distribution to EVs and additional loads, typically higher than 'EVSE Sub-Distribution Limit.' Requires an external meter to detect additional load consumption.
External Load Headroom (L1/L2/L3) [A]Safety margin to avoid transient overload situations. The algorithm will keep headroom towards 'Main Distribution Limit'.
External Load Fallback (L1/L2/L3) [A]If the external meter fails or disconnects, 'External Load Fallback' is used as the assumed consumption. A high value will stop EVSE charging due to no available current.
External Meter Location Specifies the external meter's connection location: grid entry point, between external load and installation, or at a renewable energy source (e.g., solar panel).
External Load Averaging Length [sec]Meter values will be averaged in order to avoid transients.
Current Imbalance Prevention If enabled, DLM will not exceed the 'Current Imbalance Limit' configured.
Current Imbalance Limit [A]Maximum allowed phase imbalance. DLM will not exceed the 'Current Imbalance Limit' between phases when assigning current to.
Minimum Current Limit [A]Minimum current limit that charging should not go below.
Disconnected Limit [A]Current limit when disconnected from DLM network.
IT NetworkSet to 'On' for IT (isolé-terre) systems, accepting only 'Single-phase system (IT earthing)' DLM Slaves. Set to 'Off' for other systems, accepting only DLM Slaves with different phase rotation. Incompatible DLM Slaves will be denied.
Clear persistent DLM slave DB Immediately clears the database of known DLM slaves.
Maximum Current SchedulerIf enabled, DLM will not exceed the limit configured in the time tables. Each entry set specifies the maximum allowed current for each phase which is applied at the selected hour.

3. Usage Scenarios

3.1. with external meter

Dynamic load management (DLM) must account for the total load at the house connection, including both charging currents and other household power usage. This allows for real-time adjustments in power distribution to Charging Stations.

In some cases, Grid Connection Points (GCPs) seem unsuitable for adding Charging Stations because fixed power allocation isn’t possible. Additionally, electric vehicles rarely use their maximum charging capacity, which can lead to underutilized power. Without a system to measure and allocate unused power, efficiency suffers.

The DLM continuously measures power usage at the GCP to identify reserves during periods of lower building demand (e.g., "load valleys"). It dynamically allocates this unused power to Charging Stations.

Charging current is adjustable based on the vehicle’s requirements, and the DLM ensures any unused capacity is distributed efficiently among other stations. Depending on the setup, an additional meter can be placed either after the grid operator’s meter (including EVSE sub-distribution) or within the sub-distribution (excluding EVSE sub-distribution). This setup incorporates household loads into DLM calculations, ensuring efficient and balanced power distribution.

3.2. Load Throw-Off Management

In environments with multiple consumers, some need a constant electrical supply, while others have variable electrical needs.

Without proper management, electrical supply distribution can lead to overloads or inefficient use of available power.

The load throw-off feature ensures efficient distribution of electrical supply, preventing overloads and optimizing power usage. Below are scenarios illustrating how this feature works.

Example Scenario 1: Factory with Staff Canteen and EV Chargers

A factory operates a staff canteen and provides 10 EV chargers for company fleet cars. Both facilities share a contract with load limits of 3 x 250A. During service hours, the kitchen consumes 150A on L1, 100A on L2, and 100A on L3. A signal is provided when the kitchen is not busy, and consumption falls below 10A.

In this scenario, the load throw-off process operates as follows:

  • When the kitchen is not busy, the EV charging infrastructure may consume up to 240A (250A – 10A). The control electronics provide a 12V DC signal, allowing the DLM system to use the full 3 x 240A.

  • When the kitchen is in use, the load of 140A on L1, 90A on L2, and 90A on L3 needs to be thrown off to avoid exceeding the 3 x 250A limit. In this case, the DLM may only consume 100A on L1, 150A on L2, and 150A on L3.

Configuring the Master Controller

  1. Apply the following configuration:

Location in Config UIParameterValue
Load Management >
Dynamic Load Management
Dynamic Load Management - DLM Master/Slave DLM Master (With internal DLM-Slave)
EVSE Sub Distribution (L1/L2/L3)[A]
L 1L 2L 3
240240240
External Input 1 Config Enable Opto 1 in
External Input 1 Polarity Active low
External Input 1 Current Offset
L 1L 2L 3
-140-90-90
  1. At the bottom of the Config UI, click , then click to apply the changes

Configuring the Slave Controller

  1. Apply the following configuration:

Location in Config UIParameterValue
Load Management >
Dynamic Load Management
Disconnected Limit [A]10
  1. At the bottom of the Config UI, click , then click to apply the changes

Example Scenario 2: Grid Operator with Ripple Control In this example, one or more 22kW wall boxes must reduce load to 3 x 7A (5kW) when a control signal is low.

Configuring the Master Controller

  1. Apply the following configuration:

Location in Config UISet Parameterto
Load Management >
Dynamic Load Management
Dynamic Load Management - DLM Master/Slave DLM Master (With internal DLM-Slave)
EVSE Sub Distribution Limit (L1/L2/L3)[A]
L 1L 2L 3
323232
External Input 1 Config Enable Opto 1 in
External Input 1 Polarity Active low
External Input 1 Current Offset
L 1L 2L 3
-25-25-25
Disconnected Limit [A]7
  1. At the bottom of the Config UI, click , then click to apply the changes

Configuring the Slave Controller

  1. Apply the following configuration:

Location in Config UIParameterValue
Load Management >
Dynamic Load Management
Disconnected Limit [A]7
  1. At the bottom of the Config UI, click , then click to apply the changes

Limitations of the Load throw-off function

  • The load can only be reduced instantly and not gradually over a time interval
  • With DLM active, only the current can be reduced, not the power (reduction 32A 🡒 7A, but not 22kW 🡒 5kW)

3.3. Phase-specific load management

A rechargeable electric vehicle is equipped with a built-in charger that connects to a compatible Charging Station via a cable, and can draw power from a single-phase or three-phase network.

Many competitor systems assume equal loading on all phases, regardless of actual usage, which leads to inefficient power distribution.

The DLM system detects whether the vehicle is using a single-phase or three-phase charger. For example, if a vehicle with a single-phase charger draws 16A, only the corresponding phase is used, keeping other phases available for additional charging. The system also takes phase rotation into account. For more details, see the "Phase Rotation of the ChargePoint" section.

3.4. Imbalance Prevention

In Germany, network operators must comply with technical connection conditions (TAB), which limit the apparent power of a phase to 4.6 kVA compared to the neighboring phases.

This means single-phase loads can draw a maximum of 20A if the other phases are not loaded. A skew load occurs when one phase conductor is loaded by more than 20A compared to the other two phases in a three-wire system.

To avoid skew load, it is essential to ensure that the phase currents are balanced, keeping the load within the required limits.

ExamplesPhase setupResult
1
L 1L 2L 3
101520
No difference between all outer conductors by > 20 amperes. Thus, there is no violation of the maximum allowed asymmetry.
2
L 1L 2L 3
101536
L3 is loaded 21A > L2 and 26A > L1. As a result, the max. permissible unbalanced load of 20 A is exceeded.

Electric vehicles can vary in their charging behavior, sometimes drawing over 20A even at a 3 x 32 amp Charging Station, which can lead to unbalanced loads due to a lack of communication between the vehicle's on-board charger phase and the Charging Station.

This imbalance occurs because the vehicle and Charging Station may not coordinate properly, potentially causing overloads or inefficient power usage.

Our Dynamic Load Management (DLM) system provides a solution through Current Imbalance Prevention, which monitors and corrects any asymmetry above a specified threshold. The system’s skew load limit ensures that single-phase loads over 20A are allowed if balanced across phases.
For example, three vehicles with 32-amp chargers can charge on separate phases without exceeding limits. The system detects and adjusts the current, enabling 1 x 32-amp Charging Stations or limiting unbalanced loads for 3 x 32-amp points.

3.5. The "Maximum Current Scheduler" function

In addition to the function of load management without or with an external metering, there is another function to (semi-)dynamically control the load management without external metering.

The function Maximum Current Scheduler under Load Management > Dynamic Load Management allows to determine the parameters of the Operator EVSE Sub-Distribution Limit via a time table depending on the time of day. With a known and recurring load profile, the charging currents can thus be increased or decreased at times when sufficient reserves are always available. For example, in a single-family home where 60% reserve is always available at the house connection at night, the available charging currents could be ramped up at exactly these times.

  1. To configure the Time Profile turn Maximum Current Scheduler On
  2. Click on Add Entry

At least two entries are necessary. The set currents are always valid from the set time. That means, from the entered time to the next following time this charging current is valid for the DLM. This also applies if the times are not displayed in chronological order. In the example on the right, this means that no charging current is available from 1 o'clock to 4 o'clock. Here it does not matter that the time point '1 o'clock' is at the top and the time point '4 o'clock' is at the bottom.

The times are entered according to Coordinated Universal Time (UTC). The time in Germany is therefore in winter one hour later UTC + 1 = CET - Central European Time and in summer two hours later UTC + 2 = CEST - Central European Summer Time. The fully resolved and chronologically ordered would translate into the following table:

Time: from - toDLM Current Limit (L1/L2/L3)
01:00 - 04:00
L 1L 2L 3
000
04:00 - 18:00
L 1L 2L 3
909090
18:00 - 23:00
L 1L 2L 3
100100100
23:00 - 01:00
L 1L 2L 3
150150150
  1. At the bottom of the Config UI, click , then click to apply the changes

3.6. Solar DLM

Solar DLM extends the DLM algorithm for charging stations with PV systems, allowing them to use generated solar power for charging without needing an external energy management system.

Ensure you have a basic DLM setup, an installed PV system, and an external meter measuring positive PV energy production, placed behind the inverter or at the grid connection point.

Ensure that the PV meter is placed behind the inverter or at the grid connection point. The Solar DLM algorithm prioritizes solar power for non-solar connectors first, then allocates remaining energy to solar-mode-enabled connectors to avoid using grid electricity. Solar connectors are powered on a first-come, first-served basis. Non-solar connectors charge from the PV system or grid, depending on solar production. The algorithm uses a balancing grid meter to distribute current based on production and consumption phases.

3.6.1. Configuration

  1. Log in to the Config UI using the Operator Login Credentials
  2. Apply the following configuration:

Settings for the DLM Master:

LocationParameter    Value    Info
LOAD MANAGEMENT > Dynamic Solar ChargingConfigure Solar Mode for DLMSolar ChargingThis DLM feature allows EVs on a group of DLM clients to be charged with excess PV power. Activate solar mode on one or more participating DLM clients. The function requires a meter at the grid connection point or at the solar inverter. n 'PV surplus' mode, the EV is charged when there is enough surplus power to charge at the defined minimum current. EVs in this mode charge mostly without energy from the grid. The 'PV surplus + grid support' mode uses a defined power contribution from the grid to enable charging when PV production is insufficient. This allows the vehicle to be charged primarily with self-produced energy.
Maximum grid support current [A]0Maximum grid supply current in Ampere which will be maximally used when charging solar DLM chargers in mode 'Optimized Solar Charging'
PV surplus monitoring time to resume charging [s]60When an EV is in mode 'EVSE suspended' there will be waited for a stable minimum charging current for the hold time until the EV can go back to charging. This is only used when a solar mode was enabled and the DLM slave is marked as 'solar'
Hold time after 1ph<>3ph state switching [s]very fast
fast
medium
slow
The DLM algorithm monitors the available current for the DLM slave. If the algorithm decides to switch on/off phases the current must be stable below/above the phase switching current. There are 4 modes: very fast - 1min, fast - 3min, medium - 5min, slow - 15min.
Solar mode pauseOnIf this parameter is set to 'On' the Solar DLM mode will be paused during the time span defined in parameter 'Solar DLM mode pausing time start' and 'Solar DLM mode pausing time end'.
Start time of the solar mode pause18:00When the parameter 'Solar DLM mode pausing enable' was enabled the Solar DLM will be paused from this time on.
End time of the solar mode pause18:00From the end time, the preset solar charge mode is reactivated on all charging stations configured as solar chargers.
Use solar mode on this chargerOnThis parameter is used to signal to the DLM master that the charging station is participating in solar charging. The DLM master then checks whether there is sufficient excess PV power in the current solar charging mode to charge the vehicles connected to the station. Participation in solar charging can be terminated during a charging process if desired (setting: “Off”). In this case, the normal DLM algorithm is applied.
Solar mode on this charger set by UserOnIf the role 'operator' set 'yes', the role 'user' should see the parameter on the page 'load management' and have the permission to set the 'Solar Mode on this charger' to either 'on' or 'off'.
LOAD MANAGEMENT > DLM External Measurement and InputExternal Meter LocationSpecifies how the external meter is connected depending on its location. Either at the grid entry point, between an external load and the rest of the installation, or to a renewable energy source such as a solar panel.
Software function to use phase switchingThe selected software function can exclusively use the phase switching relay. 'Off' means that phase switching between 1ph and 3ph is disabled.
Waiting time after phase switching to resume charging [s]Wait time after switching phases before closing the contactor again. Important: Some vehicles require 120s to avoid damage. Always check compatibility with the vehicle manufacturer.
Type of phase switching relay (NO/NC)The type of contactor / relay used for phase switching can be configured as normally open or normally closed.
Use phase switching relay (1ph <> 3ph)This function allows the operator to use an additional built-in relay or contactor to switch phases 2 and 3 on and off. The switch can be connected to a relay output of the charge controller. The main purpose of this function is to reduce the minimum charging power required by IEC61851-1 mode 3 from 4,140 watts to 1,380 watts. Important: not all vehicles are compatible with this function and may exhibit defects after switching.

Settings for the DLM Slave:

ParameterLocationValueInfo
Solar Mode on this charger LOAD MANAGEMENT > Dynamic Load ManagementOnEnables additional limiting for this DLM slave to use renewable production
  1. At the bottom of the Config UI, click , then click to apply the changes

4. Hierarchial DLM

Efficient load distribution and control are critical when managing power across multiple Distributed Load Management (DLM) systems, particularly when several systems rely on a limited power supply. The need arises to coordinate these systems while maintaining safety and optimizing performance.

As power demand grows, such as when multiple Charging Stations or other devices such as DC chargers are added, it becomes harder to share power safely and avoid overloading the system.

The Hierarchical Load Management (HDLM) helps by enabling a central Charge Controller to oversee several DLM systems, each with its own Master Charge Controller. It gathers information about power use, applies limits, and adjusts power sharing in real time. This ensures power is distributed safely and efficiently, starting from the main power source down to individual DLM systems.

4.1. Hardware parts

Chargers Chargers are elements that consume current and can also vary their current consumption to comply with the coordinator requests. In a “pure” setup each charger is also a participant. In a “hybrid” setup, only “masters” are participants- “slaves” are not because they do not directly communicate with the coordinator.

External loads External loads consume current but cannot be controlled. The DLM system must adjust the charger to compensate for the loads.
When external loads are present, there must be corresponding external meters to be able to estimate their contribution to the network.

External meters External (i.e. standalone) meters are set up to measure the external loads. There are two types of connection:

in line
The meter is on the line itself and measures all current passing through.

branch
The meter only measures the external load.

4.2. Creating the constraint file

The constraint configuration file defines the setup for a Hierarchical Dynamic Load Management (HDLM) system. It controls power distribution, monitors current limits, and manages the load across multiple Charging Stations and electrical lines.

Naming Scheme
Objects in the DLM system (electrical lines, meters and participants) should have a name that is unique within each category. Names have the same restrictions as domain names:

  • Between 1 and 63 characters.
  • Can contain only alphanumeric characters and dashes (no spaces).
  • Cannot start nor end with a dash.

The main components of this file are:

  1. ID
  2. Lines
  3. Groups
  4. Meters

1. ID The id is an optional field that serves as an identifier for the configuration file. It's used to validate that the daemons have loaded the correct file by matching it with the Constraints Id property in status messages.

2. Lines The lines section defines the different electrical lines and their maximum current ratings across three phases (L1, L2, L3). Each line can be described with its CurrentLimit and Parent property.

  • Root Line: The root line (e.g., main) represents the connection to the utility grid and is the central bus for the entire system.
  • Child Lines: Other lines like line1, line2, etc., branch out from the root and inherit properties from their parent unless explicitly defined.

For example:


"lines": {
"main": {
"CurrentLimit": {
"L1": 40,
"L2": 40,
"L3": 40
}
},
"line1": {
"CurrentLimit": {
"L1": 32,
"L2": 32,
"L3": 32
},
"Parent": "main"
},
"line2": {
"CurrentLimit": {
"L1": 20,
"L2": 20,
"L3": 20
},
"Parent": "main"
},
"line3": {
"CurrentLimit": {
"L1": 20,
"L2": 20,
"L3": 20
},
"Parent": "main"
}
},

line1 has a parent line called main and a specific CurrentLimit.

Handling External Loads:

In-line Loads: Use the ExternalLoadCurrent property for any line with external loads connected directly. For example:


{
"$comment": "Branch load example",
"lines": {
"main": {
"CurrentLimit": { "L1": 20, "L2": 20, "L3": 20 },
"ExternalLoadCurrent": { "L1": 20, "L2": 20, "L3": 20 },
}
},
"groups": {
"test": {
"Elements": ["c1", "c2", "c3", "c4"],
"Parent": "main"
}
},
"meters": {
"a1": {
"Model": "EEM-MB371",
"Parent": "main",
"Interface": {
"Type": "modbus-tcp",
"IPAddress": "192.168.1.53",
"TCPPort": 1505
}
}
}
}

Branch Loads: Create a virtual line without chargers that contain ExternalLoadCurrent to manage these loads separately. For example:


{
"$comment": "Branch load example",
"lines": {
"main": {
"CurrentLimit": { "L1": 20, "L2": 20, "L3": 20 }
},
"main-h1": {
"CurrentLimit": { "L1": 20, "L2": 20, "L3": 20 },
"ExternalLoadCurrent": { "L1": 20, "L2": 20, "L3": 20 },
"Parent": "main"
}
},
"groups": {
"test": {
"Elements": ["c1", "c2", "c3", "c4"],
"Parent": "main"
}
},
"meters": {
"a1": {
"Model": "EEM-MB371",
"Parent": "main-h1",
"Interface": {
"Type": "modbus-tcp",
"IPAddress": "192.168.1.53",
"TCPPort": 1505
}
}
}
}

3. Groups
The groups section defines participants (e.g., Charging Stations) that are connected to each line. Instead of specifying each participant individually, they are grouped together based on shared properties.

For example:

   "groups": {
"deck-1": {
"Elements": ["X1A", "X1B", "X1C"],
"Parent": "line1"
},
"deck-2": {
"Elements": ["X2A", "X2B", "X2C"],
"Parent": "line2"
},
"deck-3": {
"Elements": ["X3A", "X3B", "X3C"],
"Parent": "line3"
}
},

4. Meters The meters section defines any external Modbus TCP meters that monitor the system's load.

Key Properties:

  • Model: Specifies the meter model.
  • Parent: Identifies the line that the meter is connected to.
  • Interface: Provides the communication method with fields like Type (e.g., modbus-tcp), IPAddress, and optional TCPPort and SlaveID.

For example:

    "meters": {
"Main": {
"Model": "EEM-MB371",
"Parent": "main",
"Interface": {
"Type": "modbus-tcp",
"IPAddress": "10.1.2.3"
}
},
"parkingLotLight": {
"Model": "EEM-MB371",
"Parent": "line3",
"Interface": {
"Type": "modbus-tcp",
"IPAddress": "10.2.3.4"
}
}
}
}

This defines a meter monitoring the main line.

info

There can be used more than one meter. For a list of compatible meters click here.

Final Setup

{
"$schema": "./constraints.schema.json",
"lines": {
"main": {
"CurrentLimit": {
"L1": 40,
"L2": 40,
"L3": 40
}
},
"line1": {
"CurrentLimit": {
"L1": 32,
"L2": 32,
"L3": 32
},
"Parent": "main"
},
"line2": {
"CurrentLimit": {
"L1": 20,
"L2": 20,
"L3": 20
},
"Parent": "main"
},
"line3": {
"CurrentLimit": {
"L1": 20,
"L2": 20,
"L3": 20
},
"Parent": "main"
}
},
"groups": {
"deck-1": {
"Elements": ["X1A", "X1B", "X1C", "X1D", "X1E"],
"Parent": "line1"
},
"deck-2": {
"Elements": ["X2A", "X2B", "X2C"],
"Parent": "line2"
},
"deck-3": {
"Elements": ["X3A", "X3B", "X3C"],
"Parent": "line3"
}
},
"meters": {
"Main": {
"Model": "EEM-MB371",
"Parent": "main",
"Interface": {
"Type": "modbus-tcp",
"IPAddress": "10.1.2.3"
}
},
"parkingLotLight": {
"Model": "EEM-MB371",
"Parent": "line3",
"Interface": {
"Type": "modbus-tcp",
"IPAddress": "10.2.3.4"
}
}
}
}

4.3. Settings

4.3.1. Enabling Hierarchial DLM

Location in Config UIParameter             ValueInfo
LOAD MANAGEMENT >
Hierarchical Dynamic Load Management
Hierarchical Dynamic Load Management - DLM Coordinator Enabled (with local MQTT broker)Exactly one controller in the hierarchical DLM network must be selected to run the MQTT broker along with the DLM coordinator
Enabled (with remote MQTT broker)All controllers in the hierarchical DLM network must be set to "Enabled (with remote MQTT broker)." For this, you need to specify the IP address or hostname of the controller hosting the MQTT broker (refer to the "Enabled (with local MQTT broker)" setting mentioned earlier).

4.3.2. General Settings

Location in Config UIParameterValueInfo
LOAD MANAGEMENT >
Hierarchical Dynamic Load Management
TCP port of the MQTT broker8883The TCP port has to be the same for all participating controllers of the hierarchical DLM network. The default setting is set to 8883.
Unique address of the DLM master used in the hierarchical DLM Each participating controller of the hierarchical DLM network has to have a unique address corresponding to the entries from the constraints.
DLM master fallback current If a DLM master loses connection to the MQTT broker or DLM coordinator, a fallback current can be set. This serves as the maximum current for managing its connected DLM slaves across three phases (L1, L2, L3), ensuring continued load regulation and preventing overloads during the disconnection.

4.3.3. Uploading the constraint file

Location in Config UIParameterValueInfo
LOAD MANAGEMENT >
Hierarchical Dynamic Load Management
Publish constraints for DLM coordinatorOnUnder Constraints used for hierarchical DLM place the json file.